Skip to content

Cold & chilled insulation - Arlington, TX

Cold and Chilled Line Insulation in Arlington, TX and the DFW Metroplex

Chilled water at 42 to 55°F, cold process lines, glycol loops and refrigeration suction — insulated with closed-cell material and a vapor barrier that is actually continuous. On hot pipe, insulation saves fuel. On cold pipe, it is the only thing standing between the line and a ceiling that drips every July.

A DFW summer runs dew points in the 70s°F. Any surface colder than that sweats, all day, every day of the cooling season. A bare or badly sealed chilled line rains onto ceiling tiles, grows mold in the plenum, and rusts the pipe from the outside in. The fix is not thicker insulation — it is the right insulation, sealed right.

01

What we insulate

Chilled water supply and return, condenser water where it needs it, cold process piping, glycol and brine loops, and refrigeration suction lines from the machine room to the air handlers. Pumps, valves and strainers on cold service get covered too — a bare valve on a chilled line is a condensation point that drips into whatever sits under it.

We work in mechanical rooms, above ceilings, on rooftops and in pipe racks. Outdoor cold lines get the same weather-lapped metal jacketing as hot work, installed over the vapor barrier without puncturing it — the jacket takes the sun and the hail so the barrier underneath never has to.

02

Why cold lines sweat — and what the water destroys

The physics is one sentence: whenever a surface sits below the dew point of the air around it, water condenses on it. In a North Texas summer the dew point lives in the 70s°F, so a 45°F chilled line is 30 degrees below it every hour the chiller runs. That water has to go somewhere — down the pipe, through the hanger, onto the tile.

The damage compounds quietly. Stained and collapsing ceiling tiles are the visible part. Above the ceiling, the standing moisture feeds mold, and against the steel it drives corrosion under insulation — the pipe rots from the outside in, hidden under material that looks fine from below. The full mechanics are in why cold pipes sweat.

And wet insulation stops insulating. The water bridges the surface closer to the pipe temperature, which condenses more water, which soaks the run further along. A cold line with a leaking vapor barrier gets worse on its own; it never gets better on its own.

03

The vapor barrier is the job

On hot work the insulation is the point and the jacket is protection. On cold work the vapor barrier is the point. It has to be continuous over every foot of the run — every joint sealed, every seam lapped, every hanger and valve detailed. One break does not leak one spot: moisture drives toward cold, and a single open seam wicks water through the whole run behind an intact-looking surface.

So the barrier is where our hours go. Joints are sealed as they are made, not caulked afterward from the outside. Terminations get vapor stops, so if a section ever does take damage the water stays in that section instead of traveling. Fittings are fabricated to fit on our benches — a barrier that relies on tape stretched over a bunched elbow is a barrier for one summer.

04

Closed-cell material, because water is the enemy

Cold service gets closed-cell material — insulation whose cells do not connect, so the material itself cannot wick water even where the barrier takes a hit. Elastomeric foam is the workhorse on chilled water and refrigeration: flexible, its own vapor retarder, clean to fabricate around valves and pumps. Cellular glass is the heavy answer — rigid, rated −450 to 900°F, and it absorbs no water at all. It runs $28–48 per square foot installed and it is what we spec where the service is cold, wet, outdoors or all three.

What cold service does not get is fiberglass. Fiberglass on a chilled line soaks the first time the barrier is nicked, loses its R-value, and then holds that water directly against the steel — the corrosion-under-insulation case in one material. We strip and re-insulate chilled systems in exactly that condition, and the pipe underneath decides whether it was caught in time.

05

Sized by the dew point, quoted from a walk-down

Thickness on cold work is not an energy calculation — it is condensation control. The outer surface has to stay above the dew point of the worst air it lives in, or it sweats no matter how good the barrier is. A line in a conditioned space needs less; a rooftop suction line in an August design condition needs more. We size each run for its actual environment, on the conservative side.

Our calculator runs the fuel math for hot systems — cold lines do not fit that model, so they get surveyed and quoted directly. The walk-down is free: we check surface temperatures with an IR gun, find where the existing barrier has failed, and you have a written number within 24 hours. The $1,500 job minimum applies, same as all our work.

— What we offer

Closed-cell materials only

Elastomeric foam or cellular glass on cold service — material that cannot wick water even where the barrier takes damage.

A vapor barrier that is continuous

Every joint sealed as it is made, every seam lapped, vapor stops at terminations so damage stays local.

Sized for the DFW dew point

Thickness set so the surface stays above the dew point of the worst air the line lives in — not a one-size table.

Cellular glass for the hard service

Rigid, −450 to 900°F, absorbs no water at all. The spec for cold, wet and outdoor runs.

Jacket over the barrier, not through it

Metal jacketing installed without puncturing the vapor barrier — the jacket takes the abuse, the barrier stays sealed.

Free IR walk-down

We shoot the run with an IR gun, find the failed sections, and put a written number in your hand within 24 hours.

— Our work

Finished work.

Project photos on request.

We’re photographing recent work for this page. In the meantime, we’ll gladly send photos of jobs like yours.

Call (214) 603-9142

Common questions

Why is my chilled line dripping?
Its surface is below the dew point — in a DFW summer that is any surface colder than the mid-70s°F. Either the line is bare, the insulation is too thin for the environment, or the vapor barrier has a break and the insulation is soaked through. A soaked run has to be replaced, not dried; the water does not leave on its own. Full answer
Can you use fiberglass on a chilled line?
We do not. Fiberglass wicks water the first time the vapor barrier is damaged, loses its insulating value wet, and holds the moisture against the steel — that is the recipe for corrosion under insulation. Cold service gets closed-cell material: elastomeric foam or cellular glass.
How thick does cold-line insulation need to be?
Thick enough that the outer surface stays above the dew point of the air around it — that is the whole rule. It depends on the line temperature and where the line runs: a conditioned mechanical room needs less than a rooftop in August. It is a per-run calculation, not a fuel calculation, which is why we size it on the walk-down.
What does it cost?
Elastomeric work on chilled water prices comparably to hot pipe work; cellular glass runs $28–48 per square foot of finished surface installed and is the spec for the harshest service. Every job carries a $1,500 minimum. Cold lines do not go through the online calculator — we survey them and put a written number on them within 24 hours.

Get a free walk-down on your cold lines

If it drips, sweats, or the insulation feels soft, the barrier has already failed somewhere. Call (214) 603-9142 and we will find where — written estimate within 24 hours.

— Start your project

Tell us what needs wrapping.

A short form, a walk-down, and a written estimate within 24 hours. No pressure, no obligation.

or call (214) 603-9142